Waiver Requests for Golden Ocala World Equestrian Center Multi-Use Field
Original title: Golden Ocala - WEC Multi-Use Field Phase1 - Major Site Plan 32969 - Waiver to Major Site Plan in Review
Parcel #21087-001-02 #WaiverPIR-000251-2026
Tillman and Associates Engineering, LLC
LDC 6.13.6 A(3), C(3) - Stormwater quality criteria
CODE states A (3) The following systems shall be considered as meeting the County's stormwater quality criteria:(a) Systems that demonstrate numerically the post-development stormwater quality is equal to or better than the pre-development stormwater quality using methodology approved by the County Engineer or his designee. Consideration shall be for both surface water and groundwater; or (b) Dry retention systems that have a depth of four feet or less, measured from top of bank to pond bottom, and shall have a vegetative cover; or (c) Dry retention systems that have a depth of six feet or less, measured from top of bank to pond bottom, with side slopes that are no steeper than 4:1 and sodded bottoms; or(d)Wet retention/detention systems, including wetlands, that meet the governing State standards; or (e) Distributed volume. This treatment type shall provide distributed volume within each sub-basin, mimicking the pre-development sub-basin, prior to discharging to the project's stormwater quantity facility.1. The required volume to be distributed shall be a minimum of 75 percent of the difference between the post-development and the pre-development initial abstraction, not to exceed 1 inch. If the initial abstraction is less than 0.25 inches, a minimum of 0.25 inches shall be used. The initial abstraction shall be calculated using the National Resources Conservation Service Technical Release 55 (NRCS TR-55) methodology. 2.The contributing area shall be of approximately two acres or less. 3. Distributed volume shall be controlled within systems such as, shallow swales, bioretention facilities, or recessed medians located within a right-of-way, drainage right-of-way, drainage easement or conservation easement. 4. When bioretention facilities are used they shall provide retention/detention of stormwater for the basin utilizing vegetated depressions that implement landscaping and soil specifications in the design. 5. Distributed volume upstream of the receiving on-site retention/detention area shall fully recover surface storage within 72 hours. 6. There is no freeboard requirement for systems such as shallow swales, recessed medians or bioretention facilities used to solely achieve distributed volume. 7. Distributed volume shall be allowed within required buffer area if the applicant can demonstrate that the intent of the buffer can still be accomplished. 8. The seasonal high water table shall be a minimum of 1 foot below the invert of the swale or 1 foot below the bottom of the prepared soil matrix of the bioretention facility. Retention and/or detention facilities shall have a maximum depth of ten feet, as measured between the design high water elevation and the pond bottom for dry facilities, and between the design high water elevation and the normal control water elevation for wet ponds.
APPLICANT requests waiver to exceed 6-ft pond depth in DRA-16 and DRA-17. Additional storage is available within these DRAs for back to back storm events by increasing the depth to 9-ft and 7-ft, respectively.
LDC 6.13.8.B(7) - Stormwater conveyance criteria
CODE states Sizes. Stormwater conveyance pipes and cross culverts shall be a minimum of 18 inches diameter or equivalent. Driveway culverts shall be a minimum of 15 inches diameter or equivalent for residential use and a minimum of 18 inches diameter or equivalent for commercial use. Roof drains, prior to connection to the overall stormwater system, are exempt from minimum diameter requirements.
APPLICANT request - A) Request waiver for storm trunkline size to include 15'' pipe provided supporting hydraulic calculations. B) Request waiver for storm pipes sized 12'' and under for secondary system branch connections to the primary trunkline (i.e. smaller pipes for yard and roof drains) as supported by hydraulic calculations.
LDC 6.13.6.3(b) - Stormwater Quality Criteria
CODE states Dry retention systems that have a depth of four feet or less, measured from top of bank to pond bottom, and shall have a vegetative cover; or (c) Dry retention systems that have a depth of six feet or less, measured from top of bank to pond bottom, with side slopes that are no steeper than 4:1 and sodded bottoms;
APPLICANT requests waiver to use sod on pond top of banks and side slopes, and seed and mulch on pond bottoms with conditions to meet current County LDC vegetative cover requirements.
LDC 6.13.3.D(2) - DRA Maintenance berm
CODE states Commercial lots or subdivisions. Retention/detention areas shall be designed with a minimum berm width of 5 feet stabilized at six percent grade maximum around the entire perimeter of the facility and side slopes: (a) No steeper than 4:1 (horizontal: vertical); or (b) Steeper than 4:1 with an access path provided to the bottom of the facility at a slope of no steeper than 3:1; or (c) As vertical walls with a structural detail for the wall design provided, adhering to Florida Building Code, an access path provided to the bottom of the facility at a slope of no steeper than 3:1, and an appropriate barrier provided when adjacent to vehicular paths and parking areas.
APPLICANT requests waiver to provide a 5-ft min. width maintenance berm for privately owned and maintained DRAs.
LDC 2.21.1.A - Order of plan approval
CODE states A Major Site Plan shall be submitted for review and approval prior to the issuance of a Building Permit or prior to the construction of site improvements when proposed improvements exceed any of the following thresholds: (1) Collectively, all existing and proposed impervious ground coverage equals or exceeds 35 percent of the gross site area or 9,000 square feet. (2) The combined driveway trip generation meets or exceeds 50 peak hour vehicle trips. (3) A 24-inch diameter pipe, its equivalent, or larger is utilized to discharge stormwater runoff from the project area.
APPLICANT requests waiver to begin site disturbance prior to site plan approval, at the Owner's own risk, and subject to a hold placed on final inspection until the Major Site Plan is approved. No water or sewer utility work shall begin until FDEP permits are obtained.
LDC 6.13.3.C(5) - Types of Stormwater Management Facilities
CODE states A retention/detention area that is adjacent to a public right-of-way shall be constructed to be aesthetically pleasing with curvilinear form and shall be landscaped with a mixed plant pallet meeting Marion-friendly landscaping standards minimally consisting of four shade trees and 200 square feet of landscaping comprised of shrubs and/or groundcover for every 100 lineal feet of frontage or fractional part thereof, or, in the case of a wet facility, a littoral zone meeting the governing water management district criteria. The proposed landscaping shall be arranged to provide ease of maintenance and screening of stormwater structures.
APPLICANT requests waiver from curvilinear pond criteria, pond volume to be maximized to serve large outdoor areas, fields, and parking. Alternate walking and green areas are incorporated into the project site.
LDC 7.2.10 - Grease Interceptors
CODE states A. Grease interceptors shall be of an approved type and shall meet all applicable Florida Plumbing and Administrative Code specifications. B. Construction. (1) Grease interceptors shall be constructed according to Florida Administrative Code Chapter 64E-6. (2) Any grease interceptor shall not be located where vehicular traffic or other overburden loads are anticipated unless the design is approved by MCU, and the registered engineer certifies that the interceptor and soil conditions will support the anticipated loads. Where support is provided without bearing on the interceptor, bearing shall be on the soil independent from the grease interceptor and reinforced as specified by the engineer. (3) All tops shall be traffic rated where vehicular traffic patterns may occur. (4) Minimum inlet and outlet piping size is four inches. (5) Minimum slope for all tank inlet and outlet piping is 1/8 inch per foot. (6) All openings shall be sealed with a waterproof, non-shrinking grout, brushed smooth inside and outside. (7) Tanks located in areas of questionable drainage are required to have a waterproof type frame and cover, with a manhole insert. (8) Precast structures shall be inspected by MCU prior to being set into the ground. Any visible reinforcing wire, steel, or honeycombing shall be cause for rejection. (9) Precast concrete shall be coated with a corrosion inhibitor that withstands a pH level of less than 3.0. C. Maintenance access. (1) Maintenance shall be according to MCU Industrial Pretreatment Ordinance. (2) Clean outs shall be provided and installed in conformance with MCU's specifications at both the inlet and outlet to the tank(s). (3) Access to the tank(s) for cleaning and inspection shall be provided via a minimum of two, 24 inch diameter rings and covers, located at each end (inlet and outlet) of the tank. The cover shall have the word GREASE cast into it.
APPLICANT requests waiver to deviate from gravity grease interceptor in LDC, Section 7.2.10 and shown in detail "UT310 Grease Interceptor" of section 7.3.2. Proposed substitute: four (4) Schier Great Basin model GB-1000 hydro-mechanical grease interceptors in series, supported by product data and calculations, to be provided to Marion County Building Department during Building Permitting. (fewer units require using hydro-mech.).
LDC 6.14.2.C(2)(E)(1) - Connection requirements
CODE states Wastewater system. All new development shall connect to an existing central sewer system if a system with available capacity has a treatment plant or sewer line within a connection distance of 400 feet times the total number of ERCs within the project at build out. Otherwise, the project shall comply with the following as applicable: (a) New residential developments with five or more ERCs shall be serviced by a decentralized wastewater treatment system. (b) New residential developments that consist of fewer than five ERCs may use individual OSTDS in conformance with Section 6.14.3, or (c) Non-residential development with 15 or more ERCs with no food preparation and will discharge only domestic waste, shall design and construct a Wastewater Treatment Facility (WWTF) that complies with all applicable State requirements, or (d) Non-residential site developments with no food preparation with less than 15 ERCs and will discharge only domestic waste may use an OSTDS with a minimum effective septic tank capacity of two times the State requirements and an approved outlet filter is installed. (e) New and existing non-residential site developments which include cooking or food preparation on site may discharge into the system providing the food preparation wastewater is pretreated and monitored as follows: 1. The facility shall install grease removal systems that: a. Meets all applicable Florida Plumbing and Administrative Code; and b. is size supported by signed and sealed plans by the project engineer, and is approved by MCU. 2. Grease removal systems and traps shall comply with MCU Industrial Pretreatment Ordinance. (f) New and existing site developments which include the use of petroleum based products which may discharge into the system shall pretreat the wastewater as follows:1. The facility shall install an oil/water separator that: a. Meets all applicable requirements of the MCU Industrial Pretreatment Ordinance; b.is American Petroleum Institute ("API") approved; and c. is size supported by signed and sealed plans by the project engineer, and is approved by MCU. 2. Monitoring equipment (probes, sampling boxes, etc.) may be required by MCU. (g) New and existing car washes shall provide a system that uses a minimum of 80 percent recycled water. (h) New and existing facilities which have applications which may discharge hair, fur, sand, lint, and other debris shall in to the system shall pretreat the wastewater as follows: 1. The facility shall install a lint trap/sand interceptor that: a. Meets all applicable requirements set by MCU; and b. Is size supported by signed and sealed plans by the project engineer and is approved by MCU. 2. Lint trap/sand interceptors shall comply with MCU Industrial Pretreatment Ordinance.
APPLICANT requests waiver to deviate from the 1.5 x volume multiplier. The proposed Schier Great Basin model BG-1000 hydro-mechanical grease interceptor specifications has a lifetime guarantee and is made of seamless, 7/16" thick, molded polyethylene. It is understood that these interceptors have less propensity to leak than conventional concrete structure.
LDC 6.8.10.(1) - General planting requirements
CODE states (1) Native plant requirements: (a) Within the UGB, a minimum of 25 percent of all proposed plant quantities, excluding turfgrass, shall be Florida native species suitable for use in Marion County. (b) Outside of the UGB a minimum of 35 percent of all proposed plant quantities, excluding turfgrass, shall be Florida native species suitable for use in Marion County. (c) A minimum of 50 percent of the required shade trees shall be Florida native species suitable for use in Marion County. (d) To promote biological diversity, no more than 50 percent of the required shade trees for a development shall be of one species.
APPLICANT requests waiver to requirements for native species and biodiversity. Live Oaks are the predominant tree for the facility. Also, a waiver from native shrub and groundcover criteria. A plant palette for this site is being followed to match existing World Equestrian Center.
LDC 6.7.7 Tree removal procedure
CODE states A. During review of tree preservation submittals, the County's Landscape Architect or his designee may determine that modifications of the proposed plans or calculations are necessary. Conditions that may require changes include, but are not limited to, the following: (1) Preserving any tree due to their age, size, rarity, uniqueness, historic value, status as a specimen tree, or other outstanding quality. (2) Proposed grading or clearing activities do not follow the requirements of this division. (3) Proposed habitat destruction which conflicts with the requirements in Division 6.6. B. The applicant will be asked to revise and update the tree preservation information according to review comments. C. After approval, the County's Landscape Architect or his designee shall issue a tree removal permit if such tree removal is in accordance with all provisions of this Code. The approved development plans shall serve as the Tree Removal Permit.
APPLICANT request - Due to the sheer number of trees, landscape architect reviewed the quality and health of existing trees. There is a blend of individual poor health with average health existing trees. There are 1-2 excellent size trees - these are saved. But for county personal convenience- we have calculated all trees as salvageable. There are no historic trees on site.
LDC 6.8.7D - Shade tree requirement - Islands
CODE states Trees within parking areas. (1) All trees required for parking areas and vehicular use areas shall be shade trees, unless required otherwise by provisions in this section. (2) All parking lot islands, including terminal parking lot islands, shall contain one shade tree unless site lighting fixtures are proposed in said island. Double parking lot islands (where double-loaded parking bays are proposed) shall contain two shade trees. (3) In parking lot islands with site lighting fixtures, an arrangement of one or two accent/ornamental trees shall be installed depending on the size and configuration of the island. (4) Parking lot islands with control signage may contain other tree (or palm) species, in lieu of shade trees, which will not conflict with the visibility of such signage.
APPLICANT requests a waiver from internal parking islands, therefore also requesting a waiver from shade trees in internal parking islands. Project is for sports venue with very large open areas and green areas. Trees we specify are large -up to 9" caliper- 1 tree per island allows for better root growth. Additional trees will be added to perimeter to match interior island calculations.
LDC 6.7.4.D and 6.8.10.C - General planting requirements
CODE states Required shade trees shall meet the minimum size requirements in Section 6.8.10.C. which states Planting specifications are listed as follows: (1) Native plant requirements: (a) Within the UGB, a minimum of 25 percent of all proposed plant quantities, excluding turfgrass, shall be Florida native species suitable for use in Marion County. (b) Outside of the UGB a minimum of 35 percent of all proposed plant quantities, excluding turfgrass, shall be Florida native species suitable for use in Marion County. (c) A minimum of 50 percent of the required shade trees shall be Florida native species suitable for use in Marion County. (d) To promote biological diversity, no more than 50 percent of the required shade trees for a development shall be of one species. (2) The use of invasive plant species is based on the UF/IFAS Assessment of Non-native Plants (Central Zone) as updated. (a) Plant species listed as "Prohibited" are not permitted for use in any proposed development. (b) Plant species listed as "Invasive - Not Recommended" are not permitted for use in any development outside of the UGB. This group of plants may be used within the UGB with subject to approval by the County Landscape Architect. (c) Plant species listed as "Caution" may be used provided specific management strategies and monitoring are included in the project's BMP manual. (3) Trees. (a) Shade trees shall have a minimum caliper of 3.5 inches. (b) Accent or ornamental (understory) trees shall have a minimum overall height of six feet and a minimum spread of 42 inches upon installation. (4) Palms. (a) Not more than 25 percent of all required trees shall be palm trees unless a higher percentage is authorized as stated in Section 6.7.9 <https://library.municode.com/fl/marion_county/codes/land_development_code?nodeId=LADECO_ART6TESTRE_DIV7TRPRRE_S6.7.9RETR>. (b) Additional palms may be provided in excess of the 25 percent threshold when three palms are used to substitute one required tree. Where specimen palms are specified, substitution may be a one-to-one ratio. (c) Palm trees shall not be substituted for required shade trees. (d) Palms shall have a clear trunk height of 10 feet minimum. (5) Shrubs shall be a minimum height of 18 inches spaced appropriately for the species and the required screening and maintenance height. (6) Groundcovers shall be those species of plants with a mature growing height of 24 inches maximum and spaced up to 2' - 3' on-center. (7) Vining groundcovers shall have a minimum of three runners per plant. Vines may be spaced accordingly for the proposed use. (8) Turfgrass may be of any variety which is adapted and suitable for use in Marion County. The use of rolled turf is prohibited on property with public access unless the supportive netting is removed and the integrity of the turf is not jeopardized during installation.
APPLICANT request - Requirements are for the 3.5" caliper shade trees. Request waiver to install larger caliper trees but fewer quantities, based upon equivalent inch per inch of the caliper of the tree planted.
LDC 6.7.4 - Shade tree requirements
CODE states The post-development ratio of shade trees to the area of the site shall be a minimum of one shade tree per 3,000 square feet.
APPLICANT requests a waiver from one shade tree per 3,000 square feet criteria; Project requires 1416 trees per code- We have saved 297 trees with a combined caliper of 7900 plus inches. We are installing another 530 trees all over twice the size-caliper required. The sports area requires large open areas to be in scale we need the larger trees. This should compensate for the shortfall in numbers.
LDC 6.8.7 C, D, E. Parking and Vehicle use areas
CODE states C. A landscaped parking lot island shall be located every ten parking spaces and shall be a minimum of 200 square feet in size with properly drained soils. For paved parking areas within a Primary SPZ, including those with permeable or porous surfaces, parking lot islands shall be completely planted with shrubs or groundcovers; the use of turfgrass is prohibited. D. Trees within parking areas. (1) All trees required for parking areas and vehicular use areas shall be shade trees, unless required otherwise by provisions in this section. (2) All parking lot islands, including terminal parking lot islands, shall contain one shade tree unless site lighting fixtures are proposed in said island. Double parking lot islands (where double-loaded parking bays are proposed) shall contain two shade trees. (3) In parking lot islands with site lighting fixtures, an arrangement of one or two accent/ornamental trees shall be installed depending on the size and configuration of the island. (4) Parking lot islands with control signage may contain other tree (or palm) species, in lieu of shade trees, which will not conflict with the visibility of such signage. E. Each row of parking spaces shall be terminated by a landscaped island.
APPLICANT requests waiver for parking lot islands - Landscape requirements will be calculated and shifted to perimeter and linear islands. Request required for conflicts with underground drainage and large vehicle/RV/bus travel, maneuvering, and parking.
LDC 6.8.9 Service and Equipment areas
CODE states A. Utility areas and loading/unloading areas shall be screened as follows: (1) A planting area a minimum of three feet wide and shall form a continuous three-foot high landscape screen, or (2) Buffer fencing with a minimum height of three feet. B. Garbage collection areas (dumpster pad) shall be screened with a wall, buffer fencing, or a landscape screen capable of reaching a minimum height of six feet within three years. C. Trees and shrubs shall remain eight feet from any fire service connection. D. Exterior air conditioning components shall be screened by locating the equipment away from public view or through the use of a landscape screen with a minimum height of three feet.
APPLICANT request - Service, Storage, and Maintenance areas are located internal to the site, positioned away from any adjacent public roads and/or private property. Requesting a waiver from screening service and equipment areas since these areas are not visible from neighboring property.
LDC 6.11.3, Traffic Impact Analysis
CODE states A. A Traffic Impact Analysis is required to determine necessary mitigation and improvements to accommodate the proposed development. The design year shall include a minimum growth rate and in accordance with the established guidelines. For the purpose of determining what level of study must be completed, the following thresholds have been established. (1) A Traffic Statement is required for projects generating fewer than 50 peak hour trips. (2) A Traffic Assessment is required for projects generating between 50 and 99 peak hour trips. Unless the project has a four percent or more impact (percent project traffic to adopted LOS volume) on a roadway that has an existing volume/capacity (v/c) ratio of 0.80 or more, in which case a Traffic Study is required. (3) A Traffic Study is required for projects generating 100 or more peak hour trips. For projects where all impacted roadways are below 0.50 v/c a Traffic Assessment is all that is required with the exception of those projects increasing the v/c ratio on an impacted roadway by 20 percent or more.
APPLICANT - TIA has been submitted to Marion County for review and approval. Applicant requests DRC conditional site plan approval prior to approval of the Traffic Impact Analysis, at the Owner's own risk, with a hold placed upon final inspection until the TIA is approved.
LDC 6.11.5, 6.11.9.A, and 6.12.11 - Driveways, Traffic control devices and Turn lanes
CODE states General Driveway Requirements. (1) Each buildable lot, parcel, or tract is entitled to a driveway unless cross access is available. (2) Adjacent properties under the same ownership shall be considered as a single property for application of driveway spacing or for driveway permits. Applicants may include a request that properties be considered individually for permitting purposes but the request must be specifically included in the permit and a sketch included that details the lot configurations and driveway placement. (3) Driveway location and minimum spacing shall be consistent with traffic safety standards. If standards cannot be achieved, the County Engineer or his designee can review and approve on a case-by-case basis. (4) Driveway width shall be subject to internal and external traffic flow considerations. The driveway width considerations include, but are not limited to, the number of lanes, the driveway geometrics, internal obstructions, and traffic safety. (5) Concrete mitered end sections are required for culverts when used for driveways accessing a roadway with posted speeds of 40 mph or greater. C. Commercial Driveway Requirements. (1) The minimum allowed distance between a commercial driveway and the nearest intersecting roadway or driveway shall be as shown in Table 6.11-2. (2) All driveways on corner parcels must access the lower classified road unless approved by the County Engineer. Exceptions to the distances listed in Table 6.11-2 may be allowed if constraints exist that makes it impractical to meet those requirements but in no case shall that distance be less than what is shown in Table 6.11-3. (3) Driveways on the opposite side of the road from the proposed driveway shall be shown on the plan for coordination purposes. (4) All commercial driveway access shall meet FDOT sight distance requirements. A note is required on Improvement Plans and Major Site Plans stating that "sight distance at driveways complies with FDOT requirements. (5) The length of commercial driveways shall be designed to provide for an uninterrupted traffic flow on the public street. The driveway length shall be subject to the anticipated required stacking length of entering and exiting vehicles during the peak period in accordance with FDOT. (6) Commercial driveways shall be at minimum 24 feet wide within the right-of-way and have a 25-foot radius. The Office of the County Engineer may require wider driveway and radius for commercial properties with heavy truck traffic. Equivalent flare will be allowed if the projected traffic volume for the driveway is less than 600 trips per day and curb and gutter exist. (7) The maximum allowed commercial driveway grade is 10 percent. The maximum algebraic difference between two different grades is 12 percent.
CODE states A. Traffic Signals. (1) The installation of a traffic signal requires a signal warrant analysis to be performed. The County's Traffic Engineer shall determine if the signal warrant analysis justifies the need for a traffic signal. Traffic signals warranted due to the development shall be installed and paid for by the developer. (2) Justification must be provided for the left turn treatment, phases, deceleration lane lengths and timings proposed. (3) In addition to the plan requirements listed below, shop drawings with FDOT approved materials and a maintenance agreement must be provided and approved. (4) Illuminated Street Name signs shall be required at all signalized intersections. (5) A box-span configuration is required if strain poles are used. (6) Traffic signal plans shall be 11 inches by 17 inches and shall include the following. (a) A Key sheet including the name of the intersecting roads, an index, a location map, a list of the utility companies that exist in the location of the signal, and the posted speeds of the approaching roadways. (b) A Tabulation of Quantities sheet that lists the item numbers, description and quantity of materials and equipment, listed in numerical order. Pay item notes and general notes that refer to item numbers shall be shown on this sheet. (c) A General Notes sheet including all general notes, related to the specific signal, as required by the Traffic Section of the Marion County Office of the County Engineer. Contact the Office of the County Engineer for the current required general notes. (d) A Plan sheet at a scale large enough to show all details clearly and legibly. The recommended scale is 1 inch = 40 feet or 1 inch = 50 feet. The plan sheet shall include existing and proposed: 1. Edge of pavement 2. Street names 3. Drainage structures including curb and gutter and drainage inlets 4. Sidewalks and right-of-way lines 5. Pavement markings 6. Signal heads with directional arrows and movements (movement 2 and 6 shall be the major streets) 7. Detection devices such as video detection with detection field or loop detection with conduit locations 8. Pull boxes 9. Control cabinet location 10. Signal poles and span wire 11. ATMS Equipment (if applicable) 12. North arrow and scale 13. Phasing Diagram 14. Controller timings using calculated optimum timings and clearance intervals meeting FDOT requirements 15. Sign detail with dimensions of letters and sign 16. Signal head details 17. Pedestrian head details 18. FDOT pay item numbers for all equipment (e) A structural analysis with soil boring data signed and sealed by an Engineer.
CODE states Turn lanes shall be required as warranted by the project's Traffic Impact Analysis and in accordance with FDOT or as approved by the County Engineer. In addition, turn lanes shall be considered any time an unsafe condition exists or will be created. The cost of construction of such lanes shall be the responsibility of the developer. Additional right-of-way may be required and shall be dedicated by the developer and shown on the Improvement Plans and Final Plat. Any off-site improvement designs shall be submitted as an Improvement Plan application.
APPLICANT request - Driveway improvements and turn lane improvements are required for this project. Separate sets of plans will be submitted to DRC for review and approval. Applicant request DRC conditional site plan approval prior to approval of the driveway and turn lane improvement plans, at the Owner's own risk, with a hold placed upon final inspection until the driveway and turn lane improvements are approved.
LDC 2.12.4.L(3) Front page of the plan
CODE states (3) List of Development Agreements including Marion County Official Record Book and Page
APPLICANT request DRC conditional site plan approval prior to approval of Developer's Agreement, at the Owner's own risk, with a hold placed upon final inspection until the Developer's Agreement is approved or determined that it is not needed.
LDC 2.1.3 - Order of plan approval
CODE states lans listed below may be reviewed concurrently, but must be approved in the order listed below, when applicable and when the proper land use and zoning are in place: A. Master Plan. B. Preliminary Plat. C. Improvement Plan. D. Final Plat. E. Major Site Plan. However, a Major Site Plan can be substituted for the Improvement Plan and can be approved before approval of the Final Plat in cases when the infrastructure improvements supporting the plat are proposed as part of the Major Site Plan application.
APPLICANT request DRC site plan review and approval prior to submittal of updated Master Plan sheet, at the Owner's own risk. Master Plan sheet is currently under review as part of PUD amendment application.
LDC 6.4.7.E - Construction plans
CODE states Line and curve tables can be used but must be shown on the sheet to which they apply.
APPLICANT request - Code states line and curve tables can be used but must be shown on the sheet to which they apply. Applicant requests waiver for line & curve data for the project to be provided with a sketch & description prior to the request for final inspection.
LDC 6.8.8B Building landscaping
CODE states Landscape areas shall be provided adjacent to or within 25 feet from the building walls and shall extend along 60 percent of the total length of the wall, excluding those areas required for access to the building.
APPLICANT requests waiver to allow plantings adjacent to the building to be shifted to perimeter of area. This is a sports complex with larger gatherings- food court, bathroom areas, etc. Plantings will be calculated and shifted to suitable areas - out of crowd areas.
Record date · March 23, 2026
Track this bill to get notified when it advances a stage. One tap to stop, anytime.
Public stanceCommunity reactions are separate from the official record and reporting.
What This Bill Does
The developer of the Golden Ocala World Equestrian Center is requesting multiple waivers from Marion County land development codes for a new multi-use field project. These requests cover stormwater pond design, pipe sizes, landscaping requirements, and the sequence of construction approvals.
Why it matters
The project seeks to bypass standard county construction and environmental regulations to expedite development and accommodate specific site design needs for a large-scale sports complex.
Who It Affects
Groups the bill's text affects, as described in the record. Being affected is not a position for or against it.
Directly affected
Golden Ocala World Equestrian Center
The developer must secure these waivers to proceed with their specific site design and construction timeline.
Indirectly affected
Marion County Residents
Residents may be affected by changes to local stormwater management and the aesthetic/environmental standards of the development.
Key Facts
•Applicant requests to increase stormwater pond depths to 9-ft and 7-ft (exceeding the 6-ft limit) for specific drainage areas.
•Applicant requests to use 15-inch storm trunkline pipes and 12-inch pipes for secondary connections, below the standard 18-inch minimum.
•Applicant requests to begin site disturbance before formal Major Site Plan approval, at the owner's risk.
•Applicant requests to use seed and mulch on pond bottoms instead of sod.
Show all 10 facts
•Applicant requests a waiver from curvilinear pond design requirements to maximize storage volume.
•Applicant requests to use hydro-mechanical grease interceptors instead of standard gravity interceptors.
•Applicant requests to shift required landscaping and shade trees to the perimeter of the site rather than internal parking islands.
•Applicant requests to use fewer, larger-caliper trees to meet total inch-per-inch requirements instead of the standard tree count.
•Applicant requests a waiver from screening requirements for service and equipment areas, citing lack of visibility from public roads.
•Applicant requests to provide line and curve data via sketch and description later, rather than on the initial plan sheets.
Frequently Asked Questions
What is the developer asking to change regarding stormwater ponds?▾
They want to make some ponds deeper than the 6-foot limit and use seed/mulch instead of sod on the bottoms.
Can the developer start construction before the site plan is approved?▾
They are requesting permission to start site disturbance at their own risk, provided they hold off on final inspections until the plan is approved.
How will the landscaping change?▾
The developer wants to move required trees and shrubs from parking islands to the site perimeter and use fewer, larger trees to meet the total size requirements.
What else do you want to know?
News Coverage
No news coverage found yet. Articles are indexed twice daily.
Follow the record
Votes, people, money & the original source
Full breakdown
Who this bill affects and the strongest case for and against it, written only from the bill’s own text.
Patterns POLISCOPE noticed across the record. These are observations to investigate, not conclusions.
policy shift90% confidence
Cumulative Waiver Strategy
The applicant is systematically requesting waivers for almost every major category of the Land Development Code, suggesting a design that is fundamentally incompatible with current county standards.